StorEdge Battery Control

On SolarEdge StorEdge and backup-capable systems, the battery's charge and discharge behaviour can be read and written over Modbus. That covers the storage control mode, the AC charge policy, the backup reserve, and, while in Remote Control mode, the default and timed charge and discharge commands.

modbus:
  storedge_control_enabled: true

This writes to your battery

The setting is off by default. Unlike passive telemetry, changing these values affects real battery cycling.

Once enabled, the current values are published as part of the inverter payload under storedge_control.

Command topics

Nine topics accept writes:

modbus/inverter/storedge/control_mode
modbus/inverter/storedge/ac_charge_policy
modbus/inverter/storedge/ac_charge_limit
modbus/inverter/storedge/backup_reserved_setting
modbus/inverter/storedge/default_mode
modbus/inverter/storedge/command_timeout
modbus/inverter/storedge/command_mode
modbus/inverter/storedge/charge_limit
modbus/inverter/storedge/discharge_limit

A payload is either a bare value or a JSON object. Publishing 4 or {"mode": 4} to control_mode switches the battery to Remote Control mode.

Topic suffix Field Range Read-back field under storedge_control
control_mode mode 0 to 4 (0 Disabled, 1 Maximize Self Consumption, 2 Time of Use, 3 Backup Only, 4 Remote Control) storage_control_mode
ac_charge_policy policy 0 to 3 storage_ac_charge_policy
ac_charge_limit limit 0 or more, kWh or percent depending on the policy storage_ac_charge_limit
backup_reserved_setting percentage 0 to 100 storage_backup_reserved_setting
default_mode mode 0 to 7 storage_default_mode
command_timeout seconds 0 to 86400 remote_control_command_timeout
command_mode mode 0 to 7 remote_control_command_mode
charge_limit limit 0 or more, in watts remote_control_charge_limit
discharge_limit limit 0 or more, in watts remote_control_discharge_limit

The write suffixes are shorter than the read-back names on purpose. The storedge/ path segment already says which block this is, so the topics drop the redundant storage_ and remote_control_ prefixes. The read-back payload keeps the full SolarEdge protocol name of the SunSpec register.

Two different limits

charge_limit and discharge_limit here are the Remote Control power limits in watts. They are not the same as ac_charge_limit, which is the AC charging limit in kWh or percent.

When a write takes effect

control_mode, ac_charge_policy, ac_charge_limit and backup_reserved_setting always take effect.

The other five only take effect once storage_control_mode is 4, Remote Control. Writing to them in any other mode is rejected and logged, because SolarEdge ignores them there.

Skipped and forced writes

If the value you publish already matches the last value read back from the inverter, the write is skipped. These registers do not need to be exercised more than necessary.

To write anyway, for instance when you suspect the cached value is stale, add force:

{"mode": 4, "force": true}

Force only bypasses the no-op check. It does not bypass the Remote Control gate above.

Home Assistant entities

With auto discovery enabled and storedge_control_enabled: true, all nine fields appear as native entities on the inverter device:

  • Select entities for control_mode, ac_charge_policy, default_mode and command_mode. The dropdown shows SolarEdge's own mode names, and Home Assistant translates the label back to the numeric value before publishing.
  • Number entities for ac_charge_limit, backup_reserved_setting, command_timeout, charge_limit and discharge_limit.

Each entity uses the command topic documented above, so changing a value in the Home Assistant interface is the same as publishing to MQTT directly. The five Remote-Control-gated fields say so in their entity name.